Test and Repair Fire Alarm System Consilium NSAC-1

Test and Repair Fire Alarm System Consilium NSAC-1

Test and Repair Fire Alarm System Consilium NSAC-1

Specification:

1. Fire Alarm Main Control Panel

  • Brand Consilium
  • Type NSAC-1
  • Supply 230VAC and External Battery
  • Location Radio Room

2. Fire Alarm Sub Control Panel

  • Brand Minerva
  • Type NSAC-1
  • Supply 230VAC and External Battery

3. Smoke, Heat Detector and Fire Glass

  • Brand Nittan System
  • Type NS-AIHS
  • NS-AH/CS
  • NS-AIS
  • NS-AH/AIS
  • NS-ACP
  • Supply 24VDC

Error Issue:

  1. Ground Fault Indicated
  2. Detector Fault Indicated
  3. Node Fault Indicated
  4. Zone Fault Indicated
  5. Detector Units Adress not detect
Note: Between 60-70 indicative of a fault on the main panel

Solution Resulting:

1. Ground Fault possibilities as:

  • Cable installation is not feasible
  • Component on a circuit leak to the grounding
  • Detector unit that is not good.

2. Detector Fault possibly because :

Note: Some types of detector unit consists of a temperature sensor and smoke sensor.
Detector Fault may occur due to several factors, among others:
  • Damage the temperature sensor,
  • Damage the smoke sensor.
  • Damage the detector unit adresser.
Note: If one of the three factors above problems, it will display a fault on the detector concerned.

3. Node Fault possibly because:

Note: In one Node, consisting of several zone, following existing zone records:


Node 1
CPU Unit
Node 6
Display and Control Unit
Node 11
Zone 1
Zone 2
Zone 3
Zone 4
Zone5
Node 12
Zone 6


Node Fault Causes:
  • The problem occurs in the "zone", may be one or more.
  • Connection the looping connector is not good.
  • CPU internal problems.

4. Zone Fault possibly because :

Note: In one zone, consisting of several addresses, following existing address records:

Zone 1
50 number address
Node 11
1 - 50
Deck C
Zone 2
64 number address
Node 11
51 – 114
Deck B
Zone 3
54 number address
Node 11
115 – 168
Deck A
Zone 4
44 number address
Node 11
167 – 212
Main Deck
Zone 5
30 number address
Node 11
213 – 242
Engine Room
Zone 6
5 number address existing
5 number address additional
Node 12
001, 002, 005, 103, 104, 131, 132, 197, 198, 200
Engine Room, winch Room.

Zone Fault causes:
  • There is a detector that does not work properly,
  • Looping connection is not good,

5. Detector Units Address not detect.

The things that cause the detector undetected address is:
  • Detector unit is damaged, this damage consists of:
    • Component damage addresser
    • The unit is not installed correctly or tight
  • Address detector unit has not been embedded in the configuration settings in the software system.
Note: 
  • Configuration on the unit is fixed and can not be changed, the change can only be done by entering the system configuration can be done by the makers of the device, in this case is the Consilium.
  • The example in this case is on dzone 6, the existing configuration is numbered 5 address, but as many as 10 units installed detector. The system will detect that the advantages of the detector unit is a mistake.

Action Taken:

1. To resolve the issue Ground Fault

  • Checks carried out on:
    • Cable instalation,
    • Circuit in unit Main Control Panel, Annunciator Unit, and Sub Control Panel,
    • All Unit Detector.
  • Result: Ground fault problem is finished

2. To resolve the issue Detector Fault, Zone Fault, Node Fault Indicator

  • Check carried out on:
    • The first checks we did in real terms, ie by spraying smoke into the smoke detector unit.
    • And heat at a temperature detector
    • To call point unit, by pressing the ON switch.
Our first conclusion is:
    • Replacing some units detector (smoke and heat detectors)
    • Replacing some units call point
Replacement is as follows:


NS- AOHS
45 Unit
NS-CP
5 Unit
Base Plate
11     pcs



  • Result :
    • Some units still fault. Explanation of the problem: 
      • As already explained above that: in a single detector unit consists of 3 factors, consists of the smoke sensor, temperature sensor section, and address regulatory part. 
      • At first checking "only" by the method of heating the unit and spraying smoke in the unit. Regardless of address settings. So it still appears fault caused no address detection unit. As follow:

1
Fault Zone 6 Address 1 -255 Fire in Genset Room
2
Fault Zone 6 Node Number 6 in E/R
3
Fault Zone 4 Address 169 – 212
4
Fault Zone 5 Address 213 – 254
5
Fault Zone 2 Unknown Type 55 Fire In 419 Room
6
Fault Zone 5 Unknown Type 217 Fire In Pump Room
7
Fault Zone 2 Unknown Type 55 Fire In 415 Room No Answer
8
Fault Zone 3 Address 138 Fire In 315 No Answer
9
Fault Zone 3 Address 140 Fire In 310 Room Sensor Fault
10
Fault Zone 3 Address 157 Fire In Corridor Sensor Fault
11
Fault Zone 4 Address 185
12
Fault Zone 5 Unknown Type 217 Fire In Pump Room No Answer
13
Fault Zone 5 Address 213 Fire In Pump Room Sensor Fault
14
Fault Zone 5 Address 229 Fire In Equipment Store Sensor Fault
15
Fault Zone 4 Loop Input 181 Timer IN1 Cable Break
16
Fault Zone 2 Address 92 Fire In Store Sensor Fault
17
Fault Zone 2 Address 107 Fire In 441 Room Sensor Fault
18
Fault Zone 2 Address 107 Fire In Store Sensor Fault
19
Fault Zone 3 Smoke 125 Fire In 325 Room Sensor Fault
20
Fault Zone 4 Address 182 Fire In Deck Workshop Sensor Fault
21
Fault Zone 2 Unknown Type 55 Fire In 419 Communication Error
22
Fault Zone 5 Unknown Type 217 Fire In Pump Room Communication Error
23
Fault Zone 4 Loop Input 179 Timer IN1 Cable Break
24
Fault Zone 4 Address 182 Fure In Deck Workshop No Amswer
  • Solving problems still exist
    • Collecting detector units are still legible address (There are about 45 old detector from warehouse).
    • The replacement of smoke sensor and a temperature sensor on the detectors.
    • Do the cleaning on the part of the detector sensing.
    • Finish Result: There are still 4 number address that problem, namely:

1
Address 179 Zone 4
Timer
2
Address 181 Zone 4
Timer
3
Address 183 Zone 4
Address for Conventional
4
Address 165 Zone 3
Address for Conventional
  • Solving Finish: Changing the following address: the address of the Call Point unit remaining
  • Status Finish:
    • All detectors have worked well, several times performed the testing with the crew.
    • The last condition is to maximize the existing configuration, without any configuration changes that have been fixed. Because it has been explained above that the configuration of this unit is fixed from the manufacturer.
    • At the time of starting to note are: The emergence Fault Zone 6, this is due to differences in the number of items that are configured with a number of units installed. Can be set in the following manner:
MENU =MANAGEMENTZONE/UNIT”ZONE 6”MORE INFOSET AS FOUND
(Back to menu)
MENU = SERVICEOTHERRESET
This method is to declare that the Dzone 6 contained 10 units configured address
  • Note: Changes and replacement as well as the procedures for starting has been approved by the crew (captain)

Documentation

Fire Alarm Main Control Panel
Fire Alarm Main Control Panel
Smoke, Heat Detector and Fire Glass 1
Smoke, Heat Detector and Fire Glass 1
Bell Alarm
Bell Alarm
Fire Alarm Equipment Engine Room
Fire Alarm Equipment Engine Room
Fire Alarm Istallation Check
Fire Alarm Istallation Check
MCFA Circuits Consillium
MCFA Circuits Consillium
MCFA Circuits Consillium 2
MCFA Circuits Consillium 2
Smoke Detector Test
Smoke Detector Test
Materi Job :